construction and dimension

structure:compact,insert-mounting
connection:3mm connection terminal
terminal screw material:nickel plating around surface of iron(screw arrowed wrest<0.8N.m)
 shell material:burn-bear colophony
 isolation:channel isolation(input,output and power supply are isolated from each other)
zero adjustments-range:-5 to +5%
span adjustments-range:95 to 105%
power indicate light:green LED,light on when power supply
mounting:DIN rail
outline dimension(W*H*D):22.5*100*113.5mm
 weight:app.250g

1) Brief Introcucion

  LU-B11 (type F) Barriers (analogue output, 1 channel) conform to the standard of GB3836.1-2000 and GB3836.4-2000,and [Exib] IIC for explosion-proof certified. The barriers may isolate the 4-20mA d.c. control signal which from the regulator or mainipulator and then output to elctrical converter or electrical valve positioner on industrial control field, and at the same time the barriers prevent the hazardous energy from intrinsic safety terminal into hazardous area(industrial control field), to insure the system intrinsic-safety explosion-proof.

2) Technical Parameters:

2.1) main functions and features
2.1.1 compact and insert-mounting
2.1.2 output circuit intrinsically safety,[Exib]IIC if suitably certified.
2.1.3 may connect with each kind of DC signal which <20mA or <10V.
2.1.4 transfer the DC signal to isolated standard process signal, and prevent hazardous energy from

the instrinsically safety terminal into the hazardous erea.
2.1.5 with power indicator,zero & span adjustment for output signal.
2.1.6 input,output and power supply are isolated from each other.
 
2.2) input(safe-area signal)
2.2.1 current input:current:4-20mA;input resistance:50Ω(build-in)
2.2.2 voltage input:voltage:1-5V;input resistance:>=50Ω

2.3) output(hazardous-area signal)
2.3.1 current output:current:4-20mA,load resistance:<=250Ω
2.3.2 voltage output:voltage:1-5V,load resistance:>=10KΩ

2.4) intrinsically safety:
2.4.1 explosion-proof:[Exib]IIC
2.4.2 max.voltage Um:250V
2.4.3 max.output voltage Uo:30V
2.4.4 max.output current Io:30mA
2.4.5 max.external inductance Lo:7mH
2.4.6 max.external Capacity Co:0.066 uF

2.5) environmental parameters:
2.5.1 power supply:DC24V+/-10%, current consumption:2.5W when aftereffect Wpp<10%
2.5.2 temperature for operating:-20 to + 60 degree
2.5.3 humidity:10%-85% RH(none congeal)

3) performace index(to full span)

3.1 standard precision:+/-0.2%F.S
3.2 temperature drift:+/-0.02% per degree.
3.3 response time:<=0.5s(0->90%)
3.4 power voltage affect:+/-0.2%/permitted voltage range
3.5 insulated resistance:input,output and power supply are isolated from each other>=50MΩ/DC 500V
3.6 isolation intensity:input-output-power supply-ground:
     DC 1500V/1 minute(DC power)
     AC 1500V/1 minute(AC power)
3.7 load resistance affect:+/-0.2%/500Ω(when current output);+/-0.2% (when voltage output)
3.8 setting time:<=3s

4) construction and dimension

4.1 structure:compact,insert-mounting
4.2 connection:3mm connection terminal
4.3 terminal screw material:nickel plating around surface of iron(screw arrowed wrest<0.8N.m)
4.4 shell material:burn-bear colophony
4.5 isolation:channel isolation(input,output and power supply are isolated from each other)
4.6 zero adjustments-range:-5 to +5%
4.7 span adjustments-range:95 to 105%
4.8 power indicate light:green LED,light on when power supply
4.9 mounting:DIN rail
4.10 outline dimension(W*H*D):22.5*100*113.5mm
4.11 weight:app.250g

OTHER PRODUCTS
1258616562379848.jpgLU-A11 (type S) Barrier (analogue input, 1 channel)1258613360777629.jpgLU-A11 (type F) Barrier (analogue input, 1 channel)1258617675783375.jpgLU-B11 (type S) Barrier (analogue output, 1 channel)1258617906800738.jpgLU-A12 (type F) Barrier (analogue input, 1 channel)1258619728258342.jpgLU-A22 (type F) Barrier (analogue input, 2 channel)1258619853267759.jpgLU-B22 (type F) Barrier (analogue input, 2 channel)1258619991761429.jpgLU-AB22 (type F) Barrier (analogue input/output, 2 channel)1258620221175539.jpgLU-AK11 (type S) Barrier (digital input, 1 channel)1258620346952630.jpgLU-BK11 (type S) Barrier (digital output, 1 channel)1258620472124125.jpgLU-G11 Isolator/Power Supplier (1 input, 1 output)1258620632786236.jpgLU-G12 Isolator/Power Supplier (1 input, 2 output)1258620820468945.jpgLU-G22 Isolator/Power Supplier (2 input, 2 output)125867852422614.jpgLU-GR Isolator (THC input)1258678669324571.jpgLU-GZ Isolator (RTD input)1258678798651596.jpgLU-GH Isolator (slide-wire resistance input)